IL17569
Page 12-18
Once the program has been loaded the user will be instructed to
exit the flash load mode by pushing the "Exit Flash Loader Mode."
(See Figure 12-13.) The FP-5000 will display Flash Loader Mode
"Program Complete Exit FL Load Mode." Once this has been
completed the screen will prompt the user to force the relay to run
in normal mode. This is accomplished by clicking on "File" then
"Exit" to exit the Flash Loader program thus returning the FP-5000
to its normal state. (See Figure 12-14.)
If there is a message displayed on the FP-5000 that "App
checksum fail Enter FL Load Mode to erase or program" the user
will have to go back and erase the FP-5000 and reprogram
following the above steps.
Figure 12-13. Flash Programmer
Figure 12-14. Flash Programmer