Page 4-12
"IX Measured OC" Display:
IX Measured OC
51X IX TOC Curve
51X IX TOC Setting
50X-1 IX IOC 1
50X-2 IX IOC 2
"IR Residual OC" Display:
IR Residual OC
51R IR TOC Curve
51R IR TOC Setting
50R-1 IR IOC 1
50R-2 IR IOC 2
"51X IX TOC Curve" Display:
51X IX TOC Curve
Shape:
XTRM
Reset:Calc
Direction:
Both
"51X IX TOC Setting" Display:
51X IX TOC Setting
Pickup (pu):
1.00
Time Mult:
1.00
"50X-1 IX IOC 1" Display:
50X-1 IX IOC 1
Pickup (pu):
2.00
Delay (c):
Direction:
Both
"50X-2 IX IOC 2" Display:
50X-2 IX IOC 2
Pickup (pu):
3.00
Delay (c):
15
Direction:
Both
"51R IR TOC Curve" Display:
51R IR TOC Curve
Shape:
XTRM
Reset:Inst
Direction:
Both
"51R IR TOC Setting" Display:
51R IR TOC Setting
Pickup (pu):
0.10
Time Mult:
1.00
"50R-1 IR IOC 1" Display:
50R-1 IR IOC 1
Pickup (pu):
1.00
Delay (c):
60
Direction:
Both
"50R-2 IR IOC 2" Display:
50R-2 IR IOC 2
Pickup (pu):
2.00
Delay (c):
600
Direction:
Both
0