Eaton Cutler-Hammer FP-5000 Instructions Manual page 52

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

Page 5-4
Table 5.1 System Config (continued)
Display Setting
Description
Prg w/Bkr:
Program relay with breaker
open or closed (requires 52a
or 52b input)
Remote Bkr:
Enable or disable remote
breaker open/close control
from rear comm port
# Set Grps:
Select the max. number
of different Protection
Setting Groups
Set Ctrl:
Select the means of control for
selecting the active setting group
Disarm Ctrl:
Enable/disable of the
Arm/Disarm control from the front
panel "Test Mode" (Output Trip1
& Trip2 ONLY)
Energy Unit:
This is the selection for "Energy
Units" killo- or Mega- Watt-hours
TOC Reset T:
Time Overcurrent RESET Time
Delay in cycles. Used when time
option for reset is chosen
Bkr Oper PB:
Front panel Breaker Open/Close
pushbutton function Enable
This setting affects other settings. The user must save settings after changing this setting, which will take the user
1
out of program mode. The user must then re-enter program mode to continue programming the remaining settings.
If enabled, the user must go to the "Test Mode" by pressing the "test button", select Arm/Disarm Trip, then select
2
Arm Trip or Disarm Trip setting.
Ct secondary rating is automatically detected: I
3
This setting is the programmed time delay for the T Delay setting of the time overcurrent Reset setting. See TOC
4
Curve settings for 51P, 51R, and 51X elements.
Setpoint Range/
Value Selection
Open or Either
Enable or disable
1, 2, 3, or 4 1
Local, Local+
Communications,
Communications, Cin
Enable or disable 2
kWh or MWh
1 to 20 cycles 4
(Increments of 1)
Enable or disable
= 1A or 5A.
nom
IL17569
Default
Selected
Refer to
Setting
Value
Sec. #
Either
5.5.1
Disable
5.5.1
1
5.5.1
9.7
Local
5.5.1
9.7
Disable
5.5.1
11.2.5.1
kWh
5.5.1
4.6.1.3
5
5.5.1
5.5.2.1
8.3.2
Disable
5.5.1
Effective June, 2001