Logic Input Group Definitions - Eaton Cutler-Hammer FP-5000 Instructions Manual

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

Page 9-6
Table 9.5 Logic Input Group Definitions
Group
Individual Elements
Ph OC
50P-1, 50P-2, 51P
Gnd OC
50X-1, 50X-2, 50R-1, 50R-2, 51X,
51R
IOC
50X-1, 50X-2, 50R-1, 50R-2, 50P-1,
50P-2
TOC
51X, 51R, 51P
OC
50X-1, 50X-2, 50R-1, 50R-2, 50P-1,
50P-2, 51X, 51R, 51P
All Alarm
50X-3, 50R-3, 50P-3, 59-A2, 27-A2,
59-M2, 27-M2, 46-2, 47-2, 81U-2,
81O-2
Voltage
59-A1, 27-A1, 59-M1, 27-M1
Frequency
81U-1, 81O-1
All Protection
50X-1, 50X-2, 50R-1, 50R-2, 50P-1,
50P-2, 51X, 51R, 51P, 59-A1, 27-A1,
59-M1, 27-M1, 46-1, 47-1, 81U-1,
BF Pickup, Zone Gnd, Zone Phase
9.6.1 Example of Use
A simple example of the logic will illustrate the principles of
programming a logic diagram. This example shows how to add
a "High Load Alarm" function to the FP-5000.
• Set the 50P-3 Phase IOC Alarm Pickup to 85% of the 51P TOC
Pickup setting. Go to "Set Mode" Protection ! Protection Setting
Group1 ! Alarms ! 50P-3 PH IOC Alarm ! Pickup and enter a
value of 0.85.
• Use programmable logic to turn on the Auxiliary LED and energize
Output Relay 4.
• Require the 50P-3 function pickup to be present for 1 second to
prevent spurious operation.
• Maintain the output signal for 5 seconds after the current drops
below the pickup level.
• Add an external switch to Contact Input 8 to enable or disable the
High Load Alarm at the user's discretion.
A Timer Gate has an On Delay and/or an Off Delay that can be set
for up to 9999 cycles (166 minutes at 60 Hz). Use 60 cycles for an
On Delay of 1 second and 300 cycles for an Off Delay of 5 seconds.
Figure 9-5 is an implementation of the "High Load Alarm."
The logic functions are programmed as follows from the main
settings menu:
• Programmable Logic !
Logic Gate1 !
• Programmable Logic !
Timer Gate1 !
• Output Config !
Output Rly4 !
• Output Config !
Output Aux LED ! Function:
IL17569
Function:
AND
IN1:
Input CIn8
IN2:
Pickup 50P-3
In:
Logic LG1
On Delay (c):
60
Off Delay (c):
300
Function:
OR
IN1:
Logic TGI
OR
IN1:
Logic TGI
Effective June, 2001