Eaton Cutler-Hammer FP-5000 Instructions Manual page 61

Protective relay
Hide thumbs Also See for Cutler-Hammer FP-5000:
Table of Contents

Advertisement

IL17569
Table 5.3 System Alarms Phase time overcurrent (51P) and instantaneous (50P-1 & 50P-2) device settings
Display Setting
Description
Watt Power
System Watt Power Alarm Setting
Alarm
Units:
Select units for watt power
Threshold:
Select magnitude threshold
in primary units
Delay (m):
Select delay time in minutes
VAR Power
System VAR Power Alarm Setting
Alarm
Units:
Select units for VAR power
Threshold:
Select magnitude threshold
in primary units
Delay (m):
Select delay time in minutes
VA Power Alarm
System VA Power Alarm Setting
Units:
Select units for VA power
Threshold:
Select magnitude threshold
in primary units
Delay (m):
Select delay time in minutes
Watt Demand
System Watt Demand
Alarm
Alarm Setting
Units:
Select units for watt demand
Threshold:
Select magnitude threshold
in primary units
Delay (m):
Select delay time in minutes
VAR Demand
System VAR Demand
Alarm
Alarm Setting
Units:
Select units for VAR demand
Threshold:
Select magnitude threshold
in primary units
Delay (m):
Select delay time in minutes
Effective June, 2001
Setpoint Range/
Value Selection
kW or MW
1 to 40,000, Disable
(increments of 1)
0 to 60 minutes
(increments of 1)
kVAR or MVAR
1 to 40,000, Disable
(increments of 1)
0 to 60 minutes
(increments of 1)
kVA or MVA
1 to 40,000, Disable
(increments of 1)
0 to 60 minutes
(increments of 1)
kW or MW
1 to 40,000, Disable
(increments of 1)
0 to 60 minutes
(increments of 1)
kVAR or MVAR
1 to 40,000, Disable
(increments of 1)
0 to 60 minutes
(increments of 1)
Default
Selected
Refer to
Setting
Value
Sec. #
5.5.3
kW
Disable
0
5.5.3
kVAR
Disable
0
5.5.3
kVA
Disable
0
5.5.3
kW
Disable
0
5.5.3
kVAR
Disable
0
Page 5-13