WAGO 761-114 Manual page 62

Telecontrol module compact, 2 ai, web, modbus485 for wago-to-pass 761, telecontrol module for fault detection/indication, monitoring and remote control
Table of Contents

Advertisement

62
Parameterizing
Table 26: Configuring of digital inputs
Deactivation text
Address
Analog value
Delay time
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
In this field enter the text to be contained in the message
transmitted when the digital input has been reset, or when the
counted value has violated the second limit.
Use this button to select the addresses to which the message
is to be transmitted when the digital input has been reset, or
when the counted value has violated the second limit.
Click the button [Internet] for applications with GPRS
transmission.
Use these buttons to select up to four analog values which
can also be transmitted with the deactivation message when
the digital input has been reset, or when the counted value
has violated the second limit.
In these fields select the time (in hours, minutes and seconds)
by which the message is to be delayed after resetting of the
digital input.
If the input is set again before the defined delay period
elapses, no activation/deactivation message will be sent.
Enter "00:00:00" in this field to deactivate this function. The
message will then be sent immediately.
This function is available starting with Firmware Version FW
2.33.
The selection fields are active only when the input is used as
a digital input.
WAGO-TO-PASS® 761
Manual
Version 1.0.0