Modbus Interface - WAGO 761-114 Manual

Telecontrol module compact, 2 ai, web, modbus485 for wago-to-pass 761, telecontrol module for fault detection/indication, monitoring and remote control
Table of Contents

Advertisement

WAGO-TO-PASS® 761
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
5.2.5

MODBUS Interface

MODBUS Line terminator
The MODBUS specification requires a line terminator at both ends of an RS-485
bus.
If the TO-PASS
terminator must be added (e.g., directly in the D-Sub plug-in connector, or at the
bus terminals of interface module 289-966).
According to the specification, a 150Ω resistor (0.5 W) or a 1nF capacitor (at
least 10 V) and a 120Ω resistor (0.25 W) connected in series can be used for this.
If the TO-PASS
the branch cable must be kept as short as possible.
BIAS Network
Some RS-485 drivers require a BIAS network to ensure a constant status when
there is no transmission (active transmitter) on the bus.
The TO-PASS
BIAS network with two 470Ω resistors (at GND and +5 V).
Connect shielding!
Shielded cables are required for MODBUS communication. The cable shield
must be connected to the DIN rail (see section "Connections" > "Shielding").
Manual
Version 1.0.0
®
telecontrol module is operated at one end of the line, the
®
telecontrol module is operated outside the bus (not at the end),
®
telecontrol module (as the MODBUS master) is equipped with a
Connect Devices
45