Parameterizing
Table 32: Configuring the transmission repeat times
SMS Settings
SMS interval
Address
Limited SMS
transmission
Active time
Active days
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
Here, enter the cycle time in minutes to define the intervals
®
that the TO-PASS
telecontrol module is to send data to the
addresses defined under Address.
SMS content is specific to devices and firmware used and is
described in the Section "Operation – Remote Polling by
SMS".
The cyclic SMS can, for example, be used for operational
supervision.
Use this button to select the addresses to which the message
is to be transmitted in defined cycles.
Check this box to limit the SMS interval to certain days of
the week and to certain times of day.
Time adjustment must be performed for limited SMS
transmission to check the day of the week and the active
time.
The first SMS is transmitted when the starting value for the
active time on an active day is reached. The SMS is also
transmitted when a cycle time of "0" has been defined. The
transmission cycle is started when the cycle time is situated
within the active time.
This function is available starting with Firmware Version FW
2.33.
In these fields you can select the starting and end points for
the active time in "hh:mm".
The starting point must be before the end time. A selection
not in line with these requirements will be adapted
automatically.
These selection fields are active only when the box Limited
SMS transmission has been checked.
Check these boxes to mark the active days for SMS
transmission.
These boxes are active only when the Limited SMS
transmission box has been checked.