761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485

Table 32: Configuring the transmission repeat times

Web settings
Web interval
Switched interval
Switching input
Switching interval In this field enter the cycle time in minutes to define the
Web outputs
Manual
Version 1.0.0
In this field enter the cycle time in minutes to define the
intervals that the TO-PASS
data to the Internet.
Enter a "0" to deactivate cyclical data transmission.
The maximum value that you can enter here is 9999 minutes,
which corresponds to around one transmission per week.
Device-dependent function
The function is only available for devices with
GPRS functionality (device identification "Web").
Note the calculation packet size!
Please note the information given on calculation
packet size in the Section "Important Information -
Rounding of Blocks for GPRS Links."
Check this box to have the transmission interval switched as
a function of the status of a digital input between Web
interval and switching interval.
This function is available starting with Firmware Version FW
2.33.
In this field, select a digital input to be used for switching of
the transmission interval between Web interval (Off status of
the input) and the switching interval (On status of the input).
When the status of the switching input changes, the initial
transmission is triggered, followed by transmission at the
cycle time defined in the field Switching interval.
This selection field is active only when the Switched
interval box is checked.
Counter inputs may not be defined as switching
inputs
Counter inputs may not be used as switching
inputs, as no status changes are evaluated for these
inputs.
intervals that the TO-PASS
data to the Internet.
Enter a "0" to deactivate cyclical data transmission.
The maximum value that you can enter here is also 9999
minutes.
Use these buttons to select the inputs whose default setpoints
can be modified via responses from the Web portal.
This function is available starting with Firmware Version FW
2.33.
Parameterizing
®
telecontrol module is to send
®
telecontrol module is to send