Value Script Fw 2.33 (Counter Inputs); Table 45: Counter Status - WAGO 761-114 Manual

Telecontrol module compact, 2 ai, web, modbus485 for wago-to-pass 761, telecontrol module for fault detection/indication, monitoring and remote control
Table of Contents

Advertisement

108
WAGO TO-PASS® Web
10.3.1.3

Value Script FW 2.33 (Counter Inputs)

The counter inputs have resulted in counter data, signal quality and an indicator
being added to the display for the value script ("SV=02.00") and to an update of
the MODBUS registers and analog outputs.
Example:
ID=GpsLongTest;50645
&SV=02.00
&PA=0000;home ;99
&HT=1
&TI=00/01/01,00:00:37
&D1=0;0&D2=0;0&D3=0;0&D4=0;0&D5=0;0&D6=0;0&D7=0;0&D8=0;0
&A1=+00.01;mA;0&A2=+03.70;mA;0&A3=+09.87;mA;0&A4=+09.89;mA;0
&A5=+09.90;mA;0&A6=+09.89;mA;0&A7=+09.88;mA;0&A8=+09.87;mA;0
&VS=+23.97;V(Uv);0
&DO=0000
&AO=+000.0;%;+04.00;mA
&C1=0;0;0
&C2=r;20F5800;0
&C3=r;0;0
&C4=0;0;0
&SQ=21
&US=Hello
&MA=00;00;0
&MV=0026;0000;002E;0064;0026;0000;0054;0064
&HT=1: (value always 1) the device time has not been set (&TI entry is operating
hours information, started on 01.01.00 at 00:00:00), otherwise this entry is not
present.
&AO: The analog outputs are formatted with decimal places.
&Cx: Counter status[1];counter value[8];Alarm[1]
The variables for the counters are only transmitted when at least one input has
been configured as a counter.
The counter status can assume the statuses indicated by the transmitted SMS:

Table 45: Counter status

Status Explanation
0
e
d
o
r
s
c
761-114 Telecontrol Module Compact, 2 AI, Web, MODBUS485
Digital input not configured as a counter.
Counter is active.
Counter is not active.
Counter overflow.
Counter has been reset.
Counter has been started.
Counter value has been changed.
WAGO-TO-PASS® 761
Manual
Version 1.0.0