6.11.2 Setting Fault Isolation Parameters

Context
A non-intelligent rPDU does not have the fault isolation function.
Procedure
Step 1 Set parameters for BCB tripping upon battery abnormal.
1.
2.
Step 2 Set the Smart rPDU auto disconnection parameters.
1.
2.
3.
----End

6.11.3 Viewing the Power Usage

Prerequisites
Power distribution devices have been connected to the ECC800-Pro.
Procedure
Step 1 View the power information on the ECC800-Pro WebUI.
1.
2.
Issue 04 (2021-10-09)
Battery trip: Once the function is enabled, the abnormal battery string trips if
the battery pole temperature detected by the iBAT exceeds the fire protection
point. Then the battery string fault information is displayed in the power
supply and distribution link diagram.
Smart rPDU high temperature disconnection: Whenever the ECC800-Pro
detects excessive high temperature of an rPDU branch, it disconnects the
entire rPDU to protect the IT devices. Then the rPDU branch fault information
is displayed in the power supply and distribution link diagram.
Smart rPDU overcurrent disconnection: Whenever the ECC800-Pro detects
overcurrent of an rPDU branch, it disconnects the rPDU of this branch to
protect the IT devices. Then the rPDU branch fault information is displayed in
the power supply and distribution link diagram.
NO TE
Choose Monitoring > Power Distribution > iBOXn to access the Running
Parameters page.
Click Unhide All Advanced Signals, set BCB tripping upon battery
abnormal to Enabled, and click Submit.
Choose Monitoring > Cabinet > Running Parameters and click Smart
Distribution Information.
Set rPDU auto close enable to Enabled.
If the user has no special requirements, choose Monitoring > Cabinet > IT
Cabinet > rPDU > Running Parameters and retain the default value of
Branch Auto Close Current Parameter.
Log in to the ECC800-Pro WebUI as an administrator.
Choose Monitoring > Cabinet to access the Electricity Information in Each
Cabinet page.