6.6.1 FusionModule2000 Linkage Control

Prerequisites
Linkage Grouping
Table 6-38 FusionModule2000 linkage grouping
Linkage Category
● Link smoke alarm
● Open door/turn on
Link smoke alarm with
air conditioner off
Intelligent lighting
● Link fire control with
● Open door/turn on
● Link fire control with
Link high temperature
with skylight open
Issue 04 (2021-10-09)
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-
Pro is prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Ensure that Enable linkage control function is Yes.
with skylight open
lights if smoke
a
alarm
a
skylight open
lights by fire linkage
a
air conditioner off
Copyright © Huawei Technologies Co., Ltd.
Default Status
Function
on
If a smoke alarm is raised, the
smart module opens the skylights
and door and turns on lights by
default.
off
If this linkage status is set to on
and a smoke alarm is raised, the
smart cooling products shut down
automatically.
off
If this linkage status is set to on
and an infrared alarm is raised
when the camera detects human
motion or the door is opened as
authorized, the aisle lights turn on
automatically.
off
If this linkage status is set to on
and a fire occurs in the smart
module, the skylights open, lights
turn on, and the door opens
automatically, or the smart cooling
products shut down automatically.
off
If this linkage status is set to on,
the skylights open automatically
when a high temperature alarm is
raised and all smart cooling
products fail to communicate with
the ECC800-Pro.