ECC800 Data Center Controller
User Manual
Figure 3-54 iBAT3.0
Indicators
Table 3-85 Indicators
Indicator
Running
Alarm
Issue 04 (2021-10-09)
Color
Silk
Screen
Green
RUN
Red
ALM
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Off
Power consumption is low or
the iBAT is not powered on.
Blinking at
The networking has started
super short
but not completed.
intervals
Blinking at
The networking succeeds.
long intervals
Off
The iBAT is not faulty.
Steady on
● The iBAT is faulty.
● Communication with the
iBOX times out.
● No network is connected.
(The iBAT is waiting to
connect to a network.)
Blinking at
● Network parameters are
super short
being cleared.
intervals
● The iBAT is blinking.
(iBattery 2.0)
Blinking at
short
intervals
(iBattery 3.0)
3 Device Description