ECC800 Data Center Controller
User Manual
Table 8-43 Description of communications parameters to be set on a device
Parameter
Baud rate
Communications
address
Step 2 Add the device to the ECC800-Pro WebUI.
1.
2.
3.
Issue 04 (2021-10-09)
Log in to the ECC800-Pro WebUI as an administrator.
Add the device.
Table 8-44 Parameter description for adding a device
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
for adding
devices are
displayed.
Communicati
ons Port
Device
Address
Click Test Connect to check whether the device connects to the ECC800-Pro
properly.
If the connection succeeds, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection fails, check whether the device is properly connected to
the ECC800-Pro, whether the device and ECC800-Pro are running
properly, and whether the parameter settings are consistent with the
device parameters.
Copyright © Huawei Technologies Co., Ltd.
Recommended Value
This section uses 9600 as an example. Set this
parameter based on site requirements.
NOTE
For certain devices, this parameter does not need to be set.
This section uses 1 as an example. Set this parameter
based on site requirements.
Setting
Select the device attribute to be accessed
from the drop-down list box.
Select the device type to be accessed from
the drop-down list box.
Select the corresponding ETH converter
from the drop-down list box.
NOTE
Use the blinking function of the ETH converter
to identify the mapping between the device and
the ETH converter.
COM1/COM2
This section uses 1 as an example. In
practice, set this parameter to be the same
as the communications address for the
device.
8 FAQ