ECC800 Data Center Controller
User Manual
Table 6-53 Basic configuration
Parameter
Device Name
Cabinet height
Cabinet width
Power
Distribution
Parameter
Settings
rPDU-A01
rPDU-B01
Branch auto-fill mode
Issue 04 (2021-10-09)
NO TE
The settings in the following table are used as examples to describe the basic configuration.
Power system
Number of
power
supplies
Rated cabinet
power
Copyright © Huawei Technologies Co., Ltd.
Setting
Description
IT Cabinet
Set based on the actual device
101
name.
42
U space quantity of the
cabinet.
600
The width of the cabinet.
Single-phase
Set single-phase or three-
phase based on the actual
power supply.
2
rPDU quantity.
6.00
Set based on the actual rated
power of the cabinet.
PDU80001 >
Select a power distribution
1QF1(L1)
device and power distribution
branch for the rPDU
numbered rPDU-A01 in the
cabinet.
PDU80001 >
Select a power distribution
2QF1(L1)
device and power distribution
branch for the rPDU
numbered rPDU-B01 in the
cabinet.
● Ascending
● Ascending order: If the
order
branch for the first cabinet
is 1QF1(L1), 2QF1(L1), the
● Descendin
branches for subsequent
g order
cabinets are 1QF2(L2),
2QF2(L2), and the like.
● Descending order: If the
branch for the first cabinet
is 1QF10(L1), 2QF10(L1),
the branches for
subsequent cabinets are
1QF9(L3), 2QF9(L3), and
the like.
6 Feature Description
248