ECC800 Data Center Controller
User Manual
If the signal quality is poor due to signal reflection caused by long communications cables
(longer than 50 m), set toggle switch 4 to ON for the furthest independent deployment AI_DI
unit. After the DIP switch settings are modified, power off and restart the independent
deployment AI_DI unit for the new settings to take effect.
Step 2 Add an independent deployment AI_DI unit.
1.
2.
3.
----End
Issue 04 (2021-10-09)
NO TE
Log in to the ECC800-Pro WebUI as an administrator.
Add an independent deployment AI_DI unit.
Table 8-20 Adding an independent deployment AI_DI unit
Path
Parameter
Choose
Device
System
attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device. The
parameters
Communica
for adding
tions Port
devices are
displayed.
Device
Address
Click Test Connect to check whether the independent deployment AI_DI unit
connects to the ECC800-Pro properly.
a.
If the independent deployment AI_DI unit connects to the ECC800-Pro
successfully, click Confirm. The connected devices are displayed in the
Number of connected devices list.
b.
If the connection fails, check whether the independent deployment AI_DI
unit is properly connected to the ECC800-Pro, whether the independent
deployment AI_DI unit and ECC800-Pro are running properly, and
whether the parameter settings are consistent with the independent
deployment AI_DI unit parameters.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Independent Deployment AI_DI
Unit from the drop-down list box.
Select Independent Deployment AI_DI
Unit from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the
independent deployment AI_DI unit is connected
to the COM3 port on the ECC800-Pro. If the
independent deployment AI_DI unit is connected
to another port, set the COM port to the ECC800-
Pro port connected to the independent
deployment AI_DI unit.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the independent deployment
AI_DI unit based on the actual situation.
8 FAQ