ECC800 Data Center Controller
User Manual (for ECC800-Pro)

6.6 Linkage Control

6.6.1 FusionModule2000 Linkage Control

Prerequisites
Linkage Grouping
Table 6-28 FusionModule2000 linkage grouping
Linkage Category
Link smoke alarm with air
conditioner off
Intelligent lighting
Link high temperature
with skylight open
a: To link Open door/turn on lights if smoke alarm, Intelligent lighting, and Open
door/turn on lights by fire linkage, set Set light mode to Automatic on the WebUI. Path:
Monitoring > Aisle > AC Actuator Group > AC Actuator, click Running Parameters.
Issue 06 (2020-04-22)
You have obtained the IP address of the ECC800-Pro as well as the user name and
password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-Pro is
prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Ensure that Enable linkage control function is Yes.
Link smoke alarm with
skylight open
Open door/turn on
a
lights if smoke alarm
a
Link fire control with
skylight open
Open door/turn on
a
lights by fire linkage
Link fire control with
air conditioner off
Copyright © Huawei Technologies Co., Ltd.
Default Status
Function
on
If a smoke alarm is raised, the smart
module opens the skylights, access
control, and lights by default.
off
If this linkage status is set to on and a
smoke alarm is raised, the smart
cooling products turn off automatically.
If this linkage status is set to on, an
off
infrared alarm is raised when the
camera detects human motion, and the
aisle lights turn on automatically for
authorized door opening.
off
If you set this linkage status to on and a
fire occurs in the smart module, the
skylights open, lights turn on, and the
access control opens automatically, or
the smart cooling products turn off
automatically.
off
If this linkage status is set to on, the
skylights open automatically when a
high temperature alarm is raised and all
smart cooling products fail to
communicate with the ECC800-Pro.
6 Feature Description
157