5.6 Contact Output Wiring
5.6.1
Cable Specifications
5.6.2
Wiring Procedure
5-12
The converter can output a maximum of four contact signals. You can use these contact
outputs after you select the type of outputs(e.g., " low-limit alarm " or " high-limit alarm
") from the different output functions.
When using these contact outputs, install the wiring as follows:
Converter
DO-1
DO-1
DO-2
DO-2
DO-3
DO-3
DO-4
DO-4
Figure 5.11 Contact output wiring
Number of wire in cable varies depending on the number of contact used.
(1) M4 screws are used for the terminals of the converter. Each wire in the cable should
be terminated in the corresponding crimp-on terminal.
(2) The capacities of the contact output relay are 30 V DC 3 A, 250 V AC 3 A. Connect
a load (e.g. pilot lamp and annunciator) within these limits.
Terminal box
Annunciator or the like
#1 Output
#2 Output
#3 Output
#4 Output
F5.11E.EPS
IM 11M12A01-02E