7.4 Configuration of further parameters

7.4.1 Speed setting

32
Figure 30: Label position 03
6. Stick the green label [3] onto the black strip [3] and make sure that they com-
pletely overlap.
Either the AUMA Assistant App or AUMA CDT software is required to use the com-
plete range of configuration options. The user level defines which parameters are dis-
played or can be changed.
For information on the user level and their passwords, please refer to
password [} 37]
The speeds are determined by the motor speed. The motor speed and consequently
the actuator speed can be modified by means of the AUMA Assistant App, AUMA
CDT or the AUMA RSTX100 remote setting tool.
Setting is made using a percentage value within the range of 10 % and 100 %.
Thereby, 100 % corresponds to the maximum motor speed and thus to the maximum
actuator speed.
Table 13: Assignment of power levels to the motors and power supply units used
Power level
V1
V2
V3
The speed can be set individually for the following functions:
Standard speed for operations in direction OPEN and CLOSE and back (para-
meter: [PRM_5587] Motor speed 1).
Alternative standard speed if different speeds are required for operation in direc-
tions OPEN and CLOSE or if continuous changes between two specified speeds
are required (parameter: [PRM_5588] Motor speed 2).
Speeds for "Failure behaviour" and "EMERGENCY behaviour" functions:
For operation in direction CLOSE (parameter: [PRM_5592] Motor speed for
failure behaviour CLOSE and emergency operation CLOSE)
For operation in direction OPEN (parameter: [PRM_5591] Motor speed for
failure behaviour OPEN and emergency operation OPEN)
Variable speeds
For operations between OPEN and CLOSE, the speed can be specified via an ana-
logue input or the fieldbus. The analogue input must be configured to interpret this sig-
nal.
The speed can be set within the range of 10 % and 100 % of the maximum motor
speed:
Motor
18 W
25 W
50 W
User level and
Power supply unit
65 W
65 W
85 W