SYSTEM SPECIFICATIONS

Whitney Even on 06/22/2022
System Capacity
• Intelligent Signaling Line Circuits................................................1
• Addressable device capacity ..................................................198
• Programmable software zones .................................................99
• Annunciators.............................................................................16
Electrical Specifications
AC Power: 120/240 VAC, 50/60 Hz, 3.25 A. Wire size: minimum 14
AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, super-
vised.
Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger
Capacity: 7-18 AH (ES-200X cabinet holds maximum of two 18 AH
batteries.)
Communication Loop: Supervised and power-limited.
Notification Appliance Circuits: Terminal Block provides connec-
tions for four NACs, Style Y (Class B) or Style Z (Class A). Special
Application power. Power-limited, supervised circuitry. Maximum
signaling current per circuit: 2.5 amps special application, 250mA
regulated. End-of-Line Resistor: 4.7k ohm, ½ watt (P/N 71252 UL
listed) for Style Y (Class B) NAC; system capable of 1.9 kΩ - 22 kΩ
ELR range. Refer to the Fire•Lite Device Compatibility Document for
listed compatible devices.
Two Programmable Relays and One Fixed Trouble Relay: Con-
tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive).
Form-C relays, non-power-limited, non-supervised.
Cabinet Specifications
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72"
(1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29
cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00"
(55.88 cm.) high x 19.65" (49.91 cm.) wide.
Page 4 of 4 — DF-60957:A • 1/8/2018
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.
Shipping Specifications
Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) high
x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep.
Temperature and Humidity Ranges
NFPA Standards
The ES-200X complies with the following NFPA 72 Fire Alarm Sys-
tems requirements:
– LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-
sory).
– AUXILIARY (Automatic, Manual and Waterflow) (requires
4XTMF).
– REMOTE STATION (Automatic, Manual and Waterflow)
(Where a DACT is not accepted, the alarm, trouble and supervi-
sory relays may be connected to UL 864 listed transmitters. For
reverse polarity signaling of alarm and trouble, 4XTMF is
required.)
– PROPRIETARY (Automatic, Manual and Waterflow).
– CENTRAL STATION (Automatic, Manual and Waterflow, and
Sprinkler Supervised).
– OT, PSDN (Other Technologies, Packet-switched Data Net-
work)
– IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
– CBC 2007 (Seismic)
Agency Listings and Approvals
The listings and approvals below apply to the basic ES-200X control
panel. In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.
• UL: S624
NOTE: See DF-60958 for ULC-listed model.
AlarmNet®, Fire-Lite® Alarms, SWIFT®, and System Sensor® are registered
trademarks of Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation.
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.
www.firelite.com
Assembled in the USA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents