Ecom EN3 Instruction Manual page 19

Intelligent analysis
Hide thumbs Also See for ecom EN3:
Table of Contents

Advertisement

For the following steps see chapter "Data processing during the measure-
ment"
If the measured values of the subsequent gas analysis are not to be assigned
to a plant or to a customer, e.g., for a fast control measurement, confirm the
query with "No".
→ Press the <F4> key.
Then select which fuel type is used in the combustion.
Fuel type
Fuel oil
CO2max
A1
15.4
0.50
Select :
The following fuel types are stored in the instrument as standard:
Fuel type
Fuel oil
Natural gas
City gas
Coke oven gas
Liquid gas
ecom-EN3
→ To scroll through the list of fuel types stored
in the instrument, scroll up or down with the ar-
row keys.
→ Select the appropriate fuel by confirming
B
with the <Enter> key.
0.007
CO2 max
15,4
11,8
11,7
10,2
14,0
Factor A2
0,68
0,66
0,63
0,60
0,63
Factor B
0,007
0,009
0,011
0,011
0,008