Torque Seating Setting Via The Device Menu - AUMA TIGRON TR-M30X Manual

Multi-turn actuators
Hide thumbs Also See for TIGRON TR-M30X:
Table of Contents

Advertisement

Commissioning
Change settings
8.2.2.

Torque seating setting via the device menu

Information
Information
How to proceed
40
3.
Select new value via
Limit = Limit seating
Torque = Torque seating
Information: The black triangle ▶ shows the saved value. A white triangle ▷
shows the selected value which has not yet been saved.
4.
Save selected value with
The display shortly indicates Value saved!. The type of seating is set for the
end position.
5.
Press ESC (Escape) to return for further parameter setting.
If the set tripping torque is specified for the indicated operation direction, the actuator
switches off (overload protection of the valve).
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
→ The tripping torque must suit the valve.
→ Only change the setting with the consent of the valve manufacturer.
Depending on the version, the actuator settings are performed either via the Combi-
Switch or the magnetic pen control panel.
Actuators in version with Combi-Switch:
Operate the yellow shuttle dial
.
Operate the black selector switch
menu
(Enter) or to go one step back ESC (Escape).
Actuators in version with control panel for magnetic pen:
Use the magnetic pen to tap
Use the magnetic pen to tap
to go back one step, tapping ESC (Escape).
1.
Open device menu.
Information: If the ID of the indicated page starts with M, PRM, ..., you have
already entered the device menu. For further information, refer to:
page 14, Open device menu (Combi-Switch
page 15, Open device menu (magnetic pen control panel
2.
Select menu M0088 or M0089:
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Information: If required, change user level. For performing settings, at least
4 is required. For further information, refer to: ➭
user level
user level
The display indicates the command prompt CMD0018 or CMD0019.
Figure 41:
. (At least user level
4 required.)
(Enter).
of the Combi-Switch to scroll within the menu
(outer ring), either to confirm the selected