Profinet Io Fieldbus Coupler 750-375(/025-000), 750-377(/025-000); Table 40: General Module / Channel Parameters - WAGO I/O-SYSTEM 750 Manual

8ao 0-10v/±10v dc, 8-channel analog output module 0...10 v/±10 v
Table of Contents

Advertisement

67
Appendix
9.1.2.4
PROFINET IO Fieldbus Coupler
750-375(/025-000), 750-377(/025-000)
The aforementioned fieldbus couplers allow module-specific parameterization of
behavior at diagnosis.

Table 40: General module / channel parameters

Parameter
Module diagnosis
Substitute value
behavior
Substitute value
Channel x (x = 0...7)
*)
Default settings
=== Ende der Liste für Textmarke Inhalt_mitte ===
Manual
Version 1.0.0
Value
An undervoltage of the I/O module's field side power supply
*)
0 (false)
1 (true)
If an established AR, to which the submodule is assigned, is disconnected
or if the status of the "Provider State Flag" changes from "RUN" to
"STOP" in the APDU status of the consumer telegram,
according to device
*)
settings
keep last valid value
set substitute value
*)
-32767 ... 0
... 32767
WAGO-I/O-SYSTEM 750
750-597 8AO 0-10V/±10V DC
Explanation
does neither cause a transmission of a
diagnostic alarm nor an entry in the diagnostics
database of the station proxy.
entails transmission of a diagnostic alarm. This
external fault leads to an entry in the
diagnostics database of the station proxy.
the parameterized substitute value behavior of
the station proxy is applied for the duration of
missing output data. The parameterized
substitute value of the respective output
channel has no meaning in this context.
the last valid status of the respective output
channel is retained for the duration of the
missing output data. The parameterized
substitute value of the respective output
channel has no meaning in this context.
the parameterized substitute value of the
respective output channel is output for the
duration of the missing output data.
In the state of missing output data, the set
substitute value is output on the respective
output channel with the set substitute value
behavior "set substitute value".