SMA Sunny Island 5048 Installation Instructions Manual page 135

Hide thumbs Also See for Sunny Island 5048:
Table of Contents

Advertisement

SMA
Technologie AG
#260 Relay Settings
Menu
Para-
Parameter name
no.
meter
no.
#261 Relay General
#261
01
Rly1Op
#261
02
Rly2Op
#262 Relay Load
#262
01
LodSocTm1Str
#262
02
LodSocTm1Stp
#262
03
LodSocTm2Str
#262
04
LodSocTm2Stp
#262
05
LodTm1Str
#262
06
LodTm2Str
#263 Relay Timer
#263
01
RlyTmr1StrDt
#263
02
RlyTmr1StrTm
#263
03
RlyTmr1Dur
#263
04
RlyTmr1Cyc
Technical Description
Range/
Default
Short
value
descr.
AutoGn
Off
On
AutoGn
AutoLodExt
AutoLodSoc
Tmr1
Tmr2
AptPhs
GnRn
ExtVfOk
GdOn
Error
Run
Ens1
Ens2
BatFan
AcdCir
see
AutoLodSoc Function of relay 2:
#261.01
%
30
%
50
%
30
%
50
hhmmss
0
hhmmss
0
yyyymmdd
20060101 start date timer 1
hhmmss
0
hhmmss
0
Single
Single
Daily
Weekly
Parameter Lists
Description
Function of relay 1:
= switched off
= switched on
= automatic generator connection
= automatic disconnection of
external loads
= automatic disconnection of loads
due to SOC
= programmable timer 1
= programmable timer 1
= absorption phase is active
= generator is running
= ext. voltage and frequency in
permissible range
= ext. grid is connected
= error
= operation
(= currently has no function)
(= currently has no function)
= battery room fan
= electrolyte pump
for details, see #261.01
SOC limit for load shedding start for
t1
SOC limit for load shedding stop for
t1
SOC limit for load shedding start for
t2
SOC limit for load shedding stop for
t2
load shedding time 1
(begin time 1, end time 2)
load shedding time 2
(begin time 2, end time 1)
start time for relay control
timer 1
run time for relay control timer 1
repeated cycle time for timer 1
SI5048-11:EE4206
Page 135