Parameter Lists
#250 Grid Settings
Menu
Para-
Parameter name
no.
meter
no.
#250
01
GdVtgMin
#250
02
GdVtgMax
#250
03
GdCurNom
#250
04
GdFrqNom
#250
05
GdFrqMin
#250
06
GdFrqMax
#250
07
GdVldTm
#250
08
GdMod
#250
09
GdRvPwr
#250
10
GdRvTm
Page 134
SI5048-11:EE4206
Range/
Default
Short
value
descr.
V
184
V
264.5
A
16
Hz
50
Hz
47.5
Hz
50.2
sec
30
GridCharge Grid interface:
GridCharge
GridFeed
W
100
sec
5
SMA
Technologie AG
Description
minimum grid voltage
184 = 230V_50HZ
194 = 220V_60HZ
depending on the setting in QCG
maximum grid voltage
264.5 = 230V_50HZ
242 = 220V_60HZ
depending on the setting in QCG
nominal grid current
nominal grid frequency
50 = 230V_50HZ
60 = 220V_60HZ
depending on the setting in QCG
minimum grid frequency
47.5 = 230V_50HZ
59.3 = 220V_60HZ
depending on the setting in QCG
maximum grid frequency
50.2 = 230V_50HZ
60.5 = 220V_60HZ
depending on the setting in QCG
minimum time required for grid
(voltage and frequency) to be within
permissible range for connection
30 = 230V_50HZ
300 = 220V_60HZ
depending on the setting in QCG
= charging only (only current from
the grid)
= feedback also possible
permissible grid reverse power
(effective power)
permissible time for grid reverse
power
Technical Description