Parameter Lists
Menu
Para-
Parameter name
no.
meter
no.
#221
05
BatTmpStr
#222 Battery Charge Mode
#222
01
BatChrgCurMax
#222
02
AptTmBoost
#222
03
AptTmFul
#222
04
AptTmEqu
#222
05
CycTmFul
#222
06
CycTmEqu
#222
07
ChrgVtgBoost
#222
08
ChrgVtgFul
#222
09
ChrgVtgEqu
#222
10
ChrgVtgFlo
Page 130
SI5048-11:EE4206
Range/
Default
Short
value
descr.
degC
35
A
1200
min
120
h
5
h
10
d
14
d
180
V
2.4
V
2.4
V
2.4
V
2.25
SMA
Technologie AG
Description
battery restart temperature following
stop due to overtemperature
battery charging current limit
(depends on nominal battery
capacity)
absorption time for normal charge
120 = VRLA
90 = FLA
300 = NiCd
depending on the setting in QCG
absorption time for full charge
5 = VRLA
5 = FLA
7 = NiCd
depending on the setting in QCG
absorption time for equalization
charge
10 = VRLA
10 = FLA
10 = NiCd
depending on the setting in QCG
full charge cycle time
equalization charge cycle time
cell voltage nominal value for normal
charge
2.4 = VRLA
2.55 = FLA
1.65 = NiCd
depending on the setting in QCG
cell voltage nominal value for full
charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
cell voltage nominal value for
equalization charge
2.4 = VRLA
2.5 = FLA
1.65 = NiCd
depending on the setting in QCG
cell voltage nominal value for float
charge
2.25 = VRLA
2.25 = FLA
1.55 = NiCd
depending on the setting in QCG