Technical Data - SMA Sunny Island 5048 Installation Instructions Manual

Hide thumbs Also See for Sunny Island 5048:
Table of Contents

Advertisement

SMA
Technologie AG

20 Technical Data

Output data:
Nominal AC voltage (
Nominal frequency (f
Continuous AC output (P
Continuous AC output (P
AC output for 30 min at 25 °C
AC output for 5 min at 25 °C
AC output for 1 min at 25 °C
Nominal AC current (I
Max. current (peak value) for 100 ms
Harmonic distortion of output voltage (K
Power factor cosϕ
Input data
Input voltage (V
AC, ext
Input frequency (f
Max. AC input current (I
Max. input power (P
Battery data
Battery voltage (V
Max. battery charging current (I
Continuous charging current (I
Battery capacity
Charge control
Battery type
Technical Description
) (adjustable)
VAC, nom
)
nom
) at 25 °C
nom
) at 45°C
nom
)
AC, nom
) (adjustable)
) (adjustable)
ext
) (adjustable)
AC, ext
)
AC, ext
) (adjustable)
Bat, nom
Bat, max
Bat, nom
)
VAC
)
)
Technical Data
230 V (202 to 253 V)
45 to 65 Hz
5000 W
4000 W
6500 W
7200 W
8400 W
21 A
100 A (100 ms)
< 3 %
–1 to +1
230 V (172.5 to 250 V)
50 Hz (40 to 60 Hz)
56 A (2 to 56 A)
12.8 kW
48 V (41 to 63 V)
120 A
100 A
100 to 10000 Ah
IV0V process
with automatic full and
equalization charge
VRLA/FLA/NiCd
SI5048-11:EE4206
Page 155

Advertisement

Table of Contents
loading

Table of Contents