Connecting External Sources
The following process diagrams provide an overview on the start/stop behavior of the
Sunny Island 5048 during automatic generator operation:
Generator interface #242.07 GnSrtMod manual; request by Sunny
Island 5048
1
Generator requested by Sunny Island 5048
2
Manual generator start
3
Generator operation detected, warm up
phase begins
4
Warm up phase is completed, connection
5
Generator current limit
6
Minimum run time has expired
7
Current is reduced, battery absorption phase
8
Charging process is completed, request
signal is disabled
9
Manual generator stop
10 Generator is disconnected
11 Minimum run time has expired
Generator interface #242.07 GnSrtMod autostart; request by Sunny
Island 5048
1
Generator started by Sunny Island 5048
2
Generator start
3
Warm up time begins
4
Warm up time has expired
5
Generator is connected
6
Current limit
7
Minimum run time has expired
8
Current is reduced, battery absorption phase
9
Loading process is completed, generator is
disconnected
10 Generator power down time has expired,
generator is disconnected
11 Stop time has expired
Page 104
SI5048-11:EE4206
3
4
Gn
2
1
GnReq
TrfRel
ExtCur
GnWarmTm
GnRunTmMin
4
3
Gn
2
1
GnReq
5
TrfRel
ExtCur
Warm up time
Minimum run
SMA
Technologie AG
6
9
8
10
5
7
GnRunTmMax
7
10
9
8
6
Power down
Stop time
Technical Description
11
11