Menu
Para-
Parameter name
no.
meter
no.
#222
11
BatTmpCps
#222
12
AutoEquChrgEna
#223 Battery Protect Mode
#223
01
BatPro1TmStr
#223
02
BatPro1TmStp
#223
03
BatPro2TmStr
#223
04
BatPro2TmStp
#223
05
BatPro1Soc
#223
06
BatPro2Soc
#223
07
BatPro3Soc
#224 Battery Silent Mode
#224
01
SilentEna
#224
02
SilentTmFlo
(Stby)
#224
03
SilentTmMax
(Stby)
#225 Battery Current Sensor
#225
01
BatCurSnsTyp
(Stby)
#225
02
BatCurGain60
(Stby)
#225
03
BatCurGain50
(Stby)
#225
04
BatCurSnsOfs
(Stby)
Technical Description
Range/
Default
Short
value
descr.
mV/degC
4.0
Disable
Enable
Enable
h
22
h
6
h
17
h
9
%
20
%
15
%
10
Disable
Disable
Enable
h
3
h
12
None
None
60mV
50mV
A/60mV
100
A/50mV
100
A
0
Description
battery temperature compensation
absorption time for full charge
4.0 = VRLA
4.0 = FLA
0.0 = NiCd
depending on the setting in QCG
activates automatic equalization
charge
time for starting battery preservation
mode level 1
time for stopping battery preservation
mode level 1
time for starting battery preservation
mode level 2
time for stopping battery preservation
mode level 2
SOC limit for preservation mode level
1
SOC limit for preservation mode level
2
SOC limit for preservation mode level
3
allows silent mode on the grid
max. time for float charge until
transfer into silent
max. time for silent mode until
transfer into float
current sensor type (60mV, 50mV)
external battery current sensor 60mV
type (visible, if selected with
#225.01 60mV)
external battery current sensor 50mV
type (visible, if selected with
#225.01 50mV)
battery current sensor, offset error
(adjustment)
SI5048-11:EE4206