SMA Sunny Island 5048 Installation Instructions Manual page 132

Hide thumbs Also See for Sunny Island 5048:
Table of Contents

Advertisement

Parameter Lists
#230 External Settings
Menu
Para-
Parameter name
no.
meter
no.
#230
01
GnGdMod
(Stby)
#230
02
ExtLkTm
#230
03
RtCurCps
#230
04
AcSrcFrqDel
#240 Generator Settings
Menu
Para-
Parameter name
no.
meter
no.
#241 Start Settings
#241
01
GnAutoEna
#241
02
GnAutoStr
#241
03
GnSocTm1Str
#241
04
GnSocTm1Stp
#241
05
GnSocTm2Str
#241
06
GnSocTm2Stp
#241
07
GnTm1Str
#241
08
GnTm2Str
#241
09
GnPwrEna
#241
10
GnPwrStr
#241
11
GnPwrStp
#241
12
GnPwrAvgTm
Page 132
SI5048-11:EE4206
Range/
Default
Short
value
descr.
None
None
Gen
Grid
GenGrid
min
20
External
External
Internal
Shared
Hz
4.8
Range/
Default
Short
value
descr.
Off, On
On
3
%
40
%
80
%
40
%
80
hhmmss
0
hhmmss
0
Off, On
Off
kW
4
kW
2
sec
60
SMA
Technologie AG
Description
generator and grid operating mode
lock time after reverse power or relay
protection
reactive current compensation
= external (generator)
= internal (Sunny Island 5048)
= shared
frequency increase for disconnecting
AC feed-in generators
Description
activate generator autostart
number of autostarts
SOC limit for switching on generator
for time 1
SOC limit for switching off generator
for time 1
SOC limit for switching on generator
for time 2
SOC limit for switching off generator
for time 2
time 1 for generator request (begin
time 1, end time 2)
time 2 for generator request (begin
time 2, end time 1)
activate generator request as a result
of power
activates generator as a result of
power limit
deactivates generator as a result of
power limit
average time for power-related
generator start
Technical Description