SMA Sunny Island 5048 Installation Instructions Manual page 133

Hide thumbs Also See for Sunny Island 5048:
Table of Contents

Advertisement

SMA
Technologie AG
Menu
Para-
Parameter name
no.
meter
no.
#242 General Settings
#242
01
GnVtgMin
#242
02
GnVtgMax
#242
03
GnCurNom
#242
04
GnFrqNom
#242
05
GnFrqMin
#242
06
GnFrqMax
#242
07
GnStrMod
(Stby)
#242
08
GnOpTmMin
#242
09
GnStpTmMin
#242
10
GnCoolTm
#242
11
GnErrStpTm
#242
12
GnWarmTm
#242
13
GnRvPwr
#242
14
GnRvTm
#242
15
GnCtlMod
Technical Description
Range/
Default
Short
value
descr.
V
172.5
V
250
A
16
Hz
50
Hz
44.64
Hz
60
Manual
Autostart
Autostart
GenMan
min
15
min
15
min
5
h
6
sec
60
W
100
sec
30
Cur
Cur
CurFrq
Description
minimum generator voltage
172.5 = 230V_50HZ
172.5 = 220V_60HZ
depending on the setting in QCG
maximum generator voltage
250 = 230V_50HZ
250 = 220V_60HZ
depending on the setting in QCG
nominal generator current
nominal generator frequency (at
nominal load)
50 = 230V_50HZ
60 = 220V_60HZ
depending on the setting in QCG
minimum generator frequency
44.64 = 230V_50HZ
50 = 220V_60HZ
depending on the setting in QCG
maximum generator frequency
60 = 230V_50HZ
70 = 220V_60HZ
depending on the setting in QCG
generator interface
minimum generator run time
minimum generator stop time
generator cooling-off time
generator stop time for generator
fault
warm up time (minimum time required
for generator voltage and frequency
to be within permissible range for
connection)
permissible generator reverse power
(effective power)
permissible time for reverse power/
reverse current
ext. (gen/grid) controller (current
and frequency)
SI5048-11:EE4206
Parameter Lists
Page 133