NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Procedure
Step 1 On the home screen, choose Maint > Sensor Calibration.
Step 2 Fill the calibration value based on the measured error.
----End
7.1.13 Calibrating the Screen
Context
●
●
● You can calibrate the screen by DIP switch only when the system enters Quick
Settings page after the first power-on or when the system is on the home
screen.
● Touch the display screen firmly if you are using your fingertips. It is
recommended that you use the pen tip for accurate selection and quick
response.
Procedure
●
Issue 15 (2020-12-10)
You can calibrate for touching point deviation on the touchscreen.
You can calibrate the screen by tapping the screen on the Screen Calibration
page or by DIP switch.
–
Tapping the screen on the Screen Calibration page: The program of the
display board works normally; the deviation between the touching point
and the responding point is small; the Maint > Screen Calibration page
can be entered over the screen.
–
Calibrating the screen by DIP switch: The display board works normally;
the deviation between the touching point and the responding point is
unfavorably big; or the screen does not respond when being tapped.
NO TICE
When calibrating the screen by tapping the screen, tap Maint > Screen
Calibration, as shown in
screen calibration is complete.
Copyright © Huawei Technologies Co., Ltd.
Figure
7-12.
Figure 7-13
is displayed when the
7 FAQ