Huawei NetCol5000-A025 User Manual page 197

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Al
ar
m
ID
a0
2
5
a0
2
7
a0
3
8
a0
4
0
Issue 15 (2020-12-10)
Alarm
Ala
Impact
Name
rm
Sev
erit
y
Return
WA
Generates
air
RNI
an alarm
filter
NG
and shuts
blocked
down the
alarm
electric
heater and
humidifier.
Power
WA
Generates
loss
RNI
an alarm.
alarm
NG
Compre
MA
Generates
ssor
JOR
an alarm.
Liquid
pipe
temp
sensor
fault
PSU 1
MA
Generates
power
JOR
an alarm.
supply
abnorm
al
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
1. Air filters are
blocked or dirty.
2. The differential
pressure switch
is faulty.
3. An inappropriate
threshold is set
for the
differential
pressure switch.
4. The pressure
tube of the
differential
pressure switch
is blocked or
disconnected.
5. The cables to
the differential
pressure switch
are loose or
damaged.
The power supply is
cut off.
1. The cables to
the liquid pipe
temperature
sensor are loose
or damaged.
2. The liquid pipe
temperature
sensor is faulty.
The input power
cables of the PSU
are loose or
damaged.
Solution
1. Maintain or replace
the air filters.
2. Replace the
differential
pressure switch.
3. Adjust the
threshold set for
the differential
pressure switch.
4. Dredge or replace
the pressure tube.
5. Check the cables to
the differential
pressure switch.
If power failure occurs
on the power system,
no maintenance is
needed. If it occurs in
other places, check
the power supply
cables.
1. Check the cables to
the liquid pipe
temperature
sensor.
2. Maintain or replace
the liquid pipe
temperature
sensor.
Check the input
power cables of the
PSU.
187