Huawei NetCol5000-A025 User Manual page 272

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Context
The water pump is located under the wet film humidifier.
Procedure
Step 1 Tap Shutdown on the LCD home screen to turn off the smart cooling product
switch in the PDC.
● Exercise caution because the device is still energized after it is shut down on
the LCD.
● Before removing the water pump, block the water inlet pipe of the pump to
prevent water overflowing out of the water pan and water pipe.
Step 2 Open the rear door and remove the air filter.
Step 3 Cut off the ties on the water inlet pipe for the wet film humidifier.
Figure 6-35 Cutting cable ties
Step 4 Hold the release sleeve by hand and remove the water inlet pipe.
Issue 15 (2020-12-10)