Huawei NetCol5000-A025 User Manual page 207

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Al
ar
m
ID
a1
0
5
a1
1
8
a1
3
0
a1
3
4
Issue 15 (2020-12-10)
Alarm
Ala
Impact
Name
rm
Sev
erit
y
Indoor
CRI
Generates
fan
TIC
an alarm
failure
AL
and shuts
alarm
down the
smart
cooling
product.
Backup
MA
Generates
power
JOR
an alarm
failure
and shuts
alarm
down the
electric
heater.
Primary
MA
Generates
power
JOR
an alarm
failure
and shuts
alarm
down the
electric
heater.
Humid
MA
Generates
water
JOR
an alarm
inlet
and shuts
solenoi
down the
d valve
humidifier.
fault
Compre
MA
Generates
ssor
JOR
an alarm
suction
and shuts
temper
down the
ature
compressor.
sensor
fault
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
1. The
accumulated
runtime of the
fan exceeds the
alarm threshold.
2. The cable to the
fan is not
connected
properly.
3. The power
supply to the fan
is abnormal.
The power supply is
faulty.
The power supply is
faulty.
1. The cables to
the water inlet
solenoid valve
are loose or
damaged.
2. The water inlet
solenoid valve is
faulty.
1. The cables to
the suction
temperature
sensor are loose
or damaged.
2. The suction
temperature
sensor is faulty.
Solution
1. Maintain or replace
the fan, and clear
the accumulated
runtime.
2. Check the cable
connection to the
fan.
3. Check the power
supply to the fan.
Check the power
supply.
Check the power
supply.
1. Check the cables to
the water inlet
solenoid valve.
2. Replace the water
inlet solenoid
valve.
1. Check cables to the
suction
temperature
sensor.
2. Maintain or replace
the suction
temperature
sensor.
197