Huawei NetCol5000-A025 User Manual page 33

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Item
Water inlet pipe to
the humidifier
Installation Requirements
When the total load power of servers corresponding to a single smart cooling
product is less than 5 kW or the equipment room airtightness is not satisfactory,
the indoor humidity might be relatively high, which is not a product quality issue.
You are advised to install a dehumidifier in the equipment room in this case.
Table 2-6 Installation requirements
Item
Equipment room door
Floor
Installation mode
Pipe and cable
routing
Equivalent length of
one-way pipe
Height difference
between the indoor
and outdoor units
Thickness of the
thermal insulation
foam
Inner diameter of the
thermal insulation
foam
Drainage
Issue 15 (2020-12-10)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Specifications
G 1/2 inch inner screw thread
Specifications
Width ≥ 0.9 m; height ≥ 2.3 m
Bearing capacity ≥ 350 kg/m
≥ 250 mm
Installed on a concrete floor, a base, or an ESD floor
Cables and pipes can be routed from the top or bottom
≤ 80 m
● If the outdoor unit is placed higher than the indoor
unit, the maximum vertical distance between them
is 20 m.
● If the indoor unit is placed higher than the outdoor
unit, the maximum vertical distance between them
is 5 m.
≥ 13 mm
Liquid pipe: 16 mm
Gas pipe: 19 mm
Drainpipes can withstand a high temperature greater
than or equal to 85°C (for the smart cooling products
configured with electrode humidifiers)
2 Product Description
2
; height of the raised floor
23