Alarm
Ala
Impact
Name
rm
Sev
erit
y
Supply
WA
Generates
air low
RNI
an alarm.
temper
NG
ature
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
1. The temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
2. The thermal
load power is
low.
3. The ambient
temperature is
below the lower
threshold.
4. The low
temperature
alarm threshold
is inappropriate.
5. The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
6. The air filters
are blocked.
Solution
1. Adjust the
positions of the
temperature
sensors or
temperature and
humidity sensors.
2. Contact Huawei
technical support.
3. Measure the
ambient
temperature. Check
whether other
causes exist if the
alarm persists in a
long time after
startup.
4. Adjust the low
temperature alarm
threshold.
5. Calibrate or replace
the temperature
sensor or
temperature and
humidity sensor.
6. Maintain or replace
the air filters.