Huawei NetCol5000-A025 User Manual page 139

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Menu
Issue 15 (2020-12-10)
Parameter
Heating
mode
Humidifying
function
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Description
If Dehumidifying
heating is selected, the
electric heater starts
heating based on the
current temperature
only after the
dehumidification
function is enabled. If
Low-temp heating is
selected, the electric
heater starts heating
based only on the
current temperature, no
matter the
dehumidification
function is enabled or
not. If Dehumid & low-
temp heat is selected,
the electric heater starts
heating when the
dehumidification and
heating condition or the
low temperature heating
condition is met.
Enable indicates that
the electric humidifier
will be started when the
ambient humidity is
lower than the certain
humidity range of the
humidity set point.
Disable indicates that
the electric humidifier
will not be started.
Enabled when active
power indicates that the
electric humidifier will
be started when the
main power is active
and the ambient
humidity is lower than
the certain humidity
range of the humidity
set point.
Default Value
Dehumidifying
heating
Enable
129