Huawei NetCol5000-A025 User Manual page 242

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Procedure
Step 1 Tap Shutdown on the LCD home screen and turn off the switch QF3 and the
smart cooling product switch in the PDC.
● Exercise caution because the NetCol5000-A is still energized when it is being
shut down over the LCD.
● When replacing the compressor, tighten the suction angle valve to a torque of
150 N·m and the discharge angle valve to a torque of 120 N·m.
Step 2 Open the rear door and remove the air filter.
Step 3 Reclaim refrigerant.
Step 4 Remove the electric heating belt.
Step 5 Remove the compressor.
Figure 6-8 Removing a compressor
1.
Issue 15 (2020-12-10)
NO TICE
Use a flat-head screwdriver to clamp the buckle of the compressor connection
box, remove the cover of the connection box, and disconnect cables from the
compressor, as shown by (1) in
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Figure
6-8.
232