Commissioning Procedure - Huawei NetCol5000-A025 User Manual

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Figure 4-10 Modbus Settings
Step 2 Set baud rate and communication address by following instructions in
Table 4-9 Baud rate and communication address settings
Parameter
Baud rate
Communic
ation
address
----End

4.4.4 Commissioning Procedure

Context
● Remove the refrigerant steel cylinder after confirming that sufficient refrigerant
has been injected.
● Users are classified into Admin and Operator users. Admin users have more
rights than Operator users. The preset password is 000001 for both types of
users. After the first login, change the password in time to ensure account
security and prevent unauthorized network attacks, such as data tampering.
Huawei will not be liable for any security issues caused by your failure to
change the preset password in time or password loss after changing. To enter
Diagnostic Mode, log in as Admin.
● If no electric heater, humidifier, or water pump is configured, skip the
commissioning procedures for such components.
Issue 15 (2020-12-10)
Setting
9600, 19200
1–255
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Setting Method
Set the baud rate as required. The value should be
consistent with that set on the EMS.
Set the communication address of the smart
cooling product as planned. The EMS
communicates with the smart cooling product
through this address, and the communication
addresses of two smart cooling products
connecting to the same EMS must be unique.
4 Power-On Commissioning
Table
4-9.
121