Huawei NetCol5000-A025 User Manual page 126

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Paramete
r
Forced
rotation
Requireme
nt control
Issue 15 (2020-12-10)
Description
Forced rotation
specifies whether to
enable a forcible
rotation on the group
before the specified
rotation time. After a
forced rotation, the
accumulated time is
recalculated.
Enable or disable the
requirement control
for the master device.
● When the
requirement
control is Enable,
the master device
synchronizes data
(the temperature
and humidity
control type and
set points of the
master device and
other parameters)
to the slave device,
and all the smart
cooling products in
the group refer to
the mode delivered
by the master
device.
● When the
requirement
control is Disable,
the master device
does not
synchronize data to
the slave device,
and all the smart
cooling products
operate based on
their own
requirements, not
referring to the
mode delivered by
the master device.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Configuration
Principle
This item is set to No
by default. If forced
rotation is required,
the function is set to
Yes.
The requirement
control function is
recommended for the
following scenario: In
one teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same,
and device heat loads
are distributed evenly.
Default Value
No
Disable
116