NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
If the teamwork control succeeds, the teamwork topology of the smart cooling
product in the group is displayed, as shown in
the note for the screen.
Figure 4-19 Teamwork topology
Table 4-16 Notes for the screen
No.
1
2
3
4
5
Issue 15 (2020-12-10)
Parameter
Note
s
On/Off
On indicates that the smart cooling product is started and
Off indicates that the smart cooling product is shut down.
01, 02, 03
Indicates the device address. The minimum address is the
master one and the rest are all slave ones.
NOTE
If the master one offline, the online device with the smallest
address is selected to be the new master.
Active/
Active: properly responds to the requirement control.
Standby
Standby: responds to the requirement control when active
one is faulty (critical alarms, shutdown, and offline) or
cannot meet cooling requirements.
M/S
M indicates the master unit, and S indicates a slave unit.
Blue indicates that the device is operating, and gray
indicates that the device is idle.
Frame:
A device with green frame indicates the device itself, as
green/non-
green
shown in
A non-green frame indicates the other device in the group,
as shown in
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Figure
4-19.
Table 4-16
.
.
.
describes
144