NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Paramete
r
Teamwork
function
Teamwork
mode
Enable
L1/L2
linkage
Issue 15 (2020-12-10)
Description
Disable or enable the
teamwork function. If
the teamwork
function is disabled,
this device is
operating according
to its own control. If
the teamwork
function is enabled,
this device works in
harmony with others
that in the same
group.
Set the teamwork
mode. The options
include Smart and
iCooling.
Enable or disable
L1/L2 linkage.
Copyright © Huawei Technologies Co., Ltd.
4 Power-On Commissioning
Configuration
Principle
Set this parameter
based on the onsite
device heat
distribution.
Determine whether to
enable the iCooling
mode based on onsite
heat load variations.
If the heat load varies
greatly, it is
recommended that
you enable the
iCooling mode. The
parameter can only
be modified on the
ECC WebUI and
cannot be modified
on the smart cooling
product screen.
Set this parameter
based on site
requirements. The
parameter can only
be modified on the
ECC WebUI and
cannot be modified
on the smart cooling
product screen.
Default Value
Disable
Smart
Disable