Huawei NetCol5000-A025 User Manual page 205

In-row air cooled smart cooling product
Hide thumbs Also See for NetCol5000-A025:
Table of Contents

Advertisement

NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Al
ar
m
ID
a0
7
7
a0
7
9
a0
8
9
Issue 15 (2020-12-10)
Alarm
Ala
Impact
Name
rm
Sev
erit
y
Indoor
MA
Generates
fan
JOR
an alarm.
1/2/3/4
/5/6/7
fault
Drain
MA
Generates
abnorm
JOR
an alarm
al
and shuts
alarm
down the
compressor.
Compre
MA
Generates
ssor
JOR
an alarm.
drive
speed
limit
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
1. The power
supply to the fan
is abnormal.
2. The cable to the
fan is not
connected
properly.
3. The fan is faulty.
1. The drainage
filter is blocked.
2. The drainpipe is
blocked.
3. The drain pump
is faulty.
4. The low liquid
level sensor is
faulty.
1. The compressor
lacks oil.
2. The refrigerant
leaks.
Solution
1. Check the power
supply to the fan.
2. Check the cable
connection to the
fan.
3. Maintain or replace
the fan.
1. Clear the foreign
matter in the water
pan and filter.
2. Check that the
drainpipe is not
blocked or bent.
3. Check the cables to
the drain pump,
clear the foreign
matter in the
pump, or replace
the pump.
4. Check the cables to
the low liquid level
sensor, clear the
obstacles, or
replace the low
liquid level sensor.
1. Fill oil to the
compressor.
2. Identify and repair
the leaking point,
and refill
refrigerant after
maintenance.
195