NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width)
Al
ar
m
ID
a0
4
8
Issue 15 (2020-12-10)
Alarm
Ala
Impact
Name
rm
Sev
erit
y
Supply
CRI
Generates
air high
TIC
an alarm.
temper
AL
ature
alarm
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
1. The temperature
sensors or
temperature and
humidity sensors
are located in
inappropriate
positions.
2. The thermal
load power is
high or the
cooling capacity
is insufficient.
3. The ambient
temperature
exceeds the
upper threshold.
4. The high
temperature
alarm threshold
is inappropriate.
5. The value
detected by the
temperature
sensor or
temperature and
humidity sensor
is different from
the actual value.
Solution
1. Adjust the
positions of the
temperature
sensors or
temperature and
humidity sensors.
2. Add smart cooling
products or contact
Huawei technical
support.
3. Measure the
ambient
temperature. Check
whether other
causes exist if the
alarm persists in a
long time after
startup.
4. Adjust the high
temperature alarm
threshold.
5. Calibrate or replace
the temperature
sensor or
temperature and
humidity sensor.