Powering On The System - Mitsubishi Electric AnyWire ASLINK User Manual

Programmable controller
Table of Contents

Advertisement

5.9

Powering on the System

After checking the items described above, power on and start the system.
How to power on the AnyWireASLINK system is as follows.
The order is inverted when the system is powered off.
1.
24VDC external power supply for the AnyWireASLINK system
(This step is required only when the supply power of slave module is different from power supply of the NZ2AW1GNAL. When
the supply power is same as the NZ2AW1GNAL, this step is not required.)
2.
Module power supply of the NZ2AW1GNAL
3.
Power supply of the programmable controller
ON
AnyWireASLINK system
24VDC external power supply
OFF
ON
Module power supply of
the NZ2AW1GNAL
OFF
ON
Power supply of
the programmable controller
OFF
ON
Remote READY
OFF
Program
• Supply the power according to the steps: (1) 24VDC external power supply of AnyWireASLINK system, (2)
the NZ2AW1GNAL, (3) the programmable controller, or turn them on at the same time.
• If the NZ2AW1GNAL is powered on before the 24VDC external power supply in the AnyWireASLINK
system, a DP/DN disconnection error may occur.
• After Remote READY (RX0) turns on, wait at least one second to start the program.
1 second
or longer
5 INSTALLATION AND WIRING
5.9 Powering on the System
5
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2aw1gnal

Table of Contents