List of Error Codes

Error codes can be classified into the following three types.
Classification
Major error
Moderate error
Minor error
If these errors occur, check that the D LINK LED is on, and take the corrective action for the error code below.
Error code
Classification
(hexadecimal)
1020H
Minor error
1021H
Minor error
1022H
Minor error
1030H
Minor error
1041H
Minor error
1042H
Minor error
1043H
Minor error
1044H
Minor error
1045H
Minor error
1046H
Minor error
1047H
Minor error
1048H
Minor error
1049H
Minor error
104AH
Minor error
104BH
Minor error
104CH
Minor error
1050H
Minor error
1051H
Minor error
1052H
Minor error
10 TROUBLESHOOTING
122
10.6 List of Error Codes
Description
Indicates that the error is irrecoverable, and the RUN LED turns off. AnyWireASLINK transmission stops.
Indicates that operation of the module cannot continue, and the ERR. LED turns on. AnyWireASLINK transmission stops.
Indicates that operation of the module can continue, and the ERR. LED flashes.
Error name
Remote buffer
memory access
error
Number of
transmission points
of AnyWireASLINK
setting error
MODE switch
setting error
IP address setting
switch change error
MODE switch 1
change error
MODE switch 2
change error
MODE switch 3
change error
MODE switch 4
change error
MODE switch 5
change error
MODE switch 6
change error
MODE switch 7
change error
MODE switch 8
change error
MODE switch 9
change error
MODE switch 10
change error
MODE switch 11
change error
MODE switch 12
change error
Error history
storage limit error
IP address storage
limit error
Module parameter
storage limit error
Error description and cause
The SLMPSND instruction accessed
outside the range of the remote buffer
memory.
The points setting was executed from
the engineering tool while Number of
transmission points of AnyWireASLINK
was enabled.
The MODE switch is a combination that
prohibits setting.
The IP address setting switch was
changed while the module was
powered on.
MODE switch 1 was changed while the
module was powered on.
MODE switch 2 was changed while the
module was powered on.
MODE switch 3 was changed while the
module was powered on.
MODE switch 4 was changed while the
module was powered on.
MODE switch 5 was changed while the
module was powered on.
MODE switch 6 was changed while the
module was powered on.
MODE switch 7 was changed while the
module was powered on.
MODE switch 8 was changed while the
module was powered on.
MODE switch 9 was changed while the
module was powered on.
MODE switch 10 was changed while
the module was powered on.
MODE switch 11 was changed while
the module was powered on.
MODE switch 12 was changed while
the module was powered on.
The number of times that the error
history has been saved has reached
the maximum.
The number of times that an IP address
has been saved has reached the
maximum.
The number of times that the module
parameters have been saved has
reached the maximum.
Action
Correct the setting data of the SLMPSND instruction
to access within the range of the remote buffer
memory.
When executing points setting from the engineering
tool, disable Number of transmission points of
AnyWireASLINK.
Change the MODE switch to a combination that
does not prohibit setting, and power off and on the
module power supply.
Return the IP address setting switch to the setting it
had when the module power supply was turned on.
Return MODE switch 1 to the setting it had when the
module power supply was turned on.
Return MODE switch 2 to the setting it had when the
module power supply was turned on.
Return MODE switch 3 to the setting it had when the
module power supply was turned on.
Return MODE switch 4 to the setting it had when the
module power supply was turned on.
Return MODE switch 5 to the setting it had when the
module power supply was turned on.
Return MODE switch 6 to the setting it had when the
module power supply was turned on.
Return MODE switch 7 to the setting it had when the
module power supply was turned on.
Return MODE switch 8 to the setting it had when the
module power supply was turned on.
Return MODE switch 9 to the setting it had when the
module power supply was turned on.
Return MODE switch 10 to the setting it had when
the module power supply was turned on.
Return MODE switch 11 to the setting it had when
the module power supply was turned on.
Return MODE switch 12 to the setting it had when
the module power supply was turned on.
No more errors can be saved in the error history.
Check the errors with the latest error codes.
IP address changes made after this error occurs are
not saved in the non-volatile memory.
Module parameter changes made after this error
occurs are not saved in the non-volatile memory.