Mitsubishi Electric AnyWire ASLINK User Manual page 125

Programmable controller
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
1060H
Minor error
1061H
Minor error
1062H
Minor error
1063H
Minor error
1801H
Minor error
1802H
Minor error
1803H
Minor error
1804H
Minor error
1805H
Minor error
1806H
Minor error
1807H
Minor error
1808H
Minor error
1809H
Minor error
180AH
Minor error
Error name
Error description and cause
Non-volatile
An error could not be saved because
memory access
an error was detected when accessing
error (error history)
the non-volatile memory.
Non-volatile
The IP address could not be saved
memory access
because an error was detected when
error (IP address)
accessing the non-volatile memory.
Non-volatile
Module parameters could not be saved
memory access
because an error was detected when
error (module
accessing the non-volatile memory.
parameter)
Non-volatile
The slave module ID and parameter
memory data error
information saved in the non-volatile
(slave module ID,
memory are faulty.
parameter)
Bit data points
The value being set is outside the
setting range error
settable range for the bit data points
setting.
Word data use
The value being set is outside the
setting range error
settable range for the word data usage
setting.
Word data points
The value being set is outside the
setting range error
settable range for the word data points
setting.
Word data start
The value being set is outside the
address setting
settable range for the word data start
range error
address setting.
Number of word
The value being set is outside the
data points per
settable range for the number of word
frame setting range
data points setting per frame.
error
Startup operation
The value being set is outside the
mode setting range
settable range for the startup operation
error
mode setting.
Bit data double
The value being set is outside the
verification setting
settable range for the bit data double
range error
check mode setting.
Disconnection error
The value being set is outside the
automatic recovery
settable range for the disconnection
mode setting range
error automatic recovery mode setting.
error
Word input data
The value being set is outside the
hold/clear setting
settable range for the word input data
when disconnection
hold/clear setting when disconnection
occurs range error
occurs.
Output data hold/
The value being set is outside the
clear setting range
settable range for the output data hold/
error
clear setting.
Action
• Errors that occurred before this error may not have
been saved in the non-volatile memory.
• Take measures to reduce noise.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
• The IP address is not saved in the non-volatile
memory.
• Take measures to reduce noise.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
• Module parameters are not saved in the non-
volatile memory.
• Take measures to reduce noise.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
• The slave module ID and parameter information
saved in the non-volatile memory are faulty.
Execute automatic address detection again. DP/
DN disconnection detection and parameter access
cannot be performed until automatic address
detection is executed.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
Change Bit data points setting (address: 0100H) to a
setting value within the settable range, and turn on
Module parameter reflection request flag (RYC).
Change Word data use setting (address: 0101H) to a
setting value within the settable range, and turn on
Module parameter reflection request flag (RYC).
Change Word data points setting (address: 0102H)
to a setting value within the settable range, and turn
on Module parameter reflection request flag (RYC).
Change Word data start address setting (address:
0103H) to a setting value within the settable range,
and turn on Module parameter reflection request flag
(RYC).
Change Word data points setting per frame
(address: 0105H) to a setting value within the
settable range, and turn on Module parameter
reflection request flag (RYC).
Change Startup operating mode setting (address:
0107H) to a setting value within the settable range,
and turn on Module parameter reflection request flag
(RYC).
Change Double verification setting (address: 0108H)
to a setting value within the settable range, and turn
on Module parameter reflection request flag (RYC).
Change Disconnection error automatic recovery
mode setting (address: 0109H) to a setting value
within the settable range, and turn on Module
parameter reflection request flag (RYC).
Change Word input data hold/clear setting when
disconnected (address: 010AH) to a setting value
within the settable range, and turn on Module
parameter reflection request flag (RYC).
Change Output data hold/clear setting (address:
010BH) to a setting value within the settable range,
and turn on Module parameter reflection request flag
(RYC).
10 TROUBLESHOOTING
10.6 List of Error Codes
10
123

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2aw1gnal

Table of Contents