Mitsubishi Electric AnyWire ASLINK User Manual page 140

Programmable controller
Table of Contents

Advertisement

Address inspection command
■Device No.
Name
Address inspection command
■Description
When Address inspection command (RY2) is turned off and on, the automatic inspection is executed.
For details on address inspection, refer to the following.
Page 61 Address Inspection Function
Module parameter reflection request flag
■Device No.
Name
Module parameter reflection request flag
■Description
This flag is used when setting module parameters in the program.
After writing the parameter data to the remote buffer memory, turn on Module parameter reflection request flag (RYC) to write
the parameter data to the non-volatile memory.
Power off and on the system or perform the remote reset and the module starts operating with the saved settings.
AnyWireASLINK version compatibility inspection command
■Device No.
Name
AnyWireASLINK version compatibility inspection command
■Description
Turn on this signal to execute the AnyWireASLINK version compatibility inspection.
Slave module parameter access request command
■Device No.
Name
Slave module parameter access request command
■Description
Turn on this signal to perform the following operations from the NZ2AW1GNAL to a slave module.
• Read or write the parameter of the slave module.
• Execute the remote address change function.
APPX
138
Appendix 1 Remote I/O Signals
Device No.
RY2
Device No.
RYC
Device No.
RYD
Device No.
RY10

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2aw1gnal

Table of Contents