Word data points setting
■Address
Name
Word data points setting
■Description
Set the total number of word data input/output points to be used.
The word data use setting and the relationship between setting and setting value are as follows.
Setting
Not use
2 words (input 1 word, output 1 word)
4 words (input 2 words, output 2 words)
8 words (input 4 words, output 4 words)
16 words (input 8 words, output 8 words)
32 words (input 16 words, output 16 words)
64 words (input 32 words, output 32 words)
128 words (input 64 words, output 64 words)
256 words (input 128 words, output 128 words)
512 words (input 256 words, output 256 words)
1024 words (input 512 words, output 512 words)
If Word data use setting (address: 0101H) is 0000H (Not use), set this setting to 0000H (Not use) also.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Word data points
setting range error (error code: 1803H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are the same as those for the word data use setting.
Page 151 Word data use setting
Word data start address setting
■Address
Name
Word data start address setting
■Description
The set value becomes the word data start address.
The settable range is 0 to 511. (Initial value: 0000H)
If word data is not to be used, set the word address to 0.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Word data start
address setting range error (error code: 1804H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are the same as those for the word data use setting.
Page 151 Word data use setting
APPX
152
Appendix 3 Remote Buffer Memory
Address
0102H
Setting value
0000H (initial value)
0001H
0002H
0003H
0004H
0005H
0006H
0007H
0008H
0009H
000AH
Address